Sprinkler firefighting system

  • Bulb operating. red- 68°C, yellow- 79°C, Green- 93°C
  • At least 2 source of power for Seawater pump, alarm and detection system and Fresh water pump
  • Sprinkler must be resistant to corrosion
  • Each section not to contain more than 200 sprinkler head,
  • Each sprinkler must be sufficient to cover area of 16 ㎡
  • Farthest sprinkler head not less than 4.8 bar pressure
  • Gauge should be provided at each section and central station
  • Paint locker room must have sprinkler connected to fire main pump

Hyper mist firefighting system

  • Protect spaces, M/E, A/E, purifier room, incinerator, boiler platform
  • Activation give visual and audible alarm.